Special Occupancies
1. Gas explosion-proof equipment is always approved in a class II location.
(a) True
(b) False
2. In Class II Div. 1, EMT conduit is permitted if used with a sealing fitting.
(a) True
(b) False
3. It is permissible to use multiwire circuits in Class II Div. 1 locations.
(a) True
(b) False
4. Cable bus is approved for Class III Div. 1 locations.
(a) True
(b) False
5. TEFC motors are approved for Class III Div. 1 and Div. 2.
(a) True
(b) False
6. In a class II div. 2 location, luminaires shall be dust-tight or identified for the location.
(a) True
(b) False
Answers:
1. (b) Not unless identified for the Class II location, Ref: 502.5
2. (b) Not permitted, Ref: 502.10(A)
3. (a) Deleted previous requirement
4. (a) Ref: 503.10(A)(5)
5. (a) Ref: 503.125
6. (a) Ref: 501.130(B)(2)